Effect of ventilation improvement during a tuberculosis outbreak in underventilated university buildings

Chun Ru Du, Shun Chih Wang, Ming Chih Yu, Ting Fang Chiu, Jann Yuan Wang, Pei Chun Chuang, Ruwen Jou, Pei Chun Chan, Chi Tai Fang

研究成果: 雜誌貢獻文章同行評審

40 引文 斯高帕斯(Scopus)

摘要

The role of ventilation in preventing tuberculosis (TB) transmission has been widely proposed in infection control guidance. However, conclusive evidence is lacking. Modeling suggested the threshold of ventilation rate to reduce effective reproductive ratio (ratio between new secondary infectious cases and source cases) of TB to below 1 is corresponding to a carbon dioxide (CO2) level of 1000 parts per million (ppm). Here, we measured the effect of improving ventilation rate on a TB outbreak involving 27 TB cases and 1665 contacts in underventilated university buildings. Ventilation engineering decreased the maximum CO2 levels from 3204 ± 50 ppm to 591-603 ppm. Thereafter, the secondary attack rate of new contacts in university dropped to zero (mean follow-up duration: 5.9 years). Exposure to source TB cases under CO2 >1000 ppm indoor environment was a significant risk factor for contacts to become new infectious TB cases (P <.001). After adjusting for effects of contact investigation and latent TB infection treatment, improving ventilation rate to levels with CO2 <1000 ppm was independently associated with a 97% decrease (95% CI: 50%-99.9%) in the incidence of TB among contacts. These results show that maintaining adequate indoor ventilation could be a highly effective strategy for controlling TB outbreaks.
原文英語
頁(從 - 到)422-432
頁數11
期刊Indoor Air
30
發行號3
DOIs
出版狀態已發佈 - 5月 1 2020

ASJC Scopus subject areas

  • 環境工程
  • 建築與營造
  • 公共衛生、環境和職業健康

指紋

深入研究「Effect of ventilation improvement during a tuberculosis outbreak in underventilated university buildings」主題。共同形成了獨特的指紋。

引用此